2-25 Installation of ProLiant Storage System /U
Compaq ProLiant Storage System /U User Guide
Airflow Requirements
Compaq ProLiant rackmount servers draw cool air in through the front door
and exhaust warm air out the rear. Therefore, the front door of the rack must be
adequately ventilated to allow ambient room air to enter the cabinet, and the
rear door must be adequately ventilated to allow the warm air to escape from
the cabinet. Do not block the ventilation apertures.
CAUTION:
If a third-party rack is used, the following minimum requirements
should be observed to ensure adequate airflow and to prevent damage to the
equipment:
Front: The front must have a minimum of 25 inches of unrestricted
ventilation.
Side: The clearance between the installed module and the side panels of the
rack should be a minimum of 2.75 inches.
Rear: The clearance between the back of the rack and the wall should be a
minimum of 30 inches, and the equipment should be operating without a rear
door.
Blanking Panels
If all of the vertical space in the rack is not filled by components, the gaps that
are left will cause a change in airflow through the rack and across the
components. These gaps need to be covered with blanking panels.