Compaq AlphaServer DS20 Manual de Serviço Página 43

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 42
System Overview 1-33
When AC is applied to the system, Vaux (auxiliary voltage) is asserted and is sensed
on the server feature module. If the On-Off Button is On, and RCM OK and Interlock
OK are asserted, the OCP asserts DC_ENABLE_L starting the power supplies. If
there is a hard fault on power-up, the power supplies shut down immediately;
otherwise, the power system powers up and remains up until the system is shut off or
the server feature module senses a fault. If a power fault is sensed, the signal
SHUTDOWN is asserted after a 30 second delay. Cycling the On-Off button can
restore the power. If the system powers up and shuts off in approximately 30 seconds,
the server feature module has sensed a fault and a fan (system or CPU) is likely
broken.
Vista de página 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 181 182

Comentários a estes Manuais

Sem comentários